KSEF ECOWATT

Simple flow AHU

Modular - Reaction - ECM < 12 000 m3/h

KSEF ECOWATT

Simple flow AHU


Modular - Reaction - ECM < 12 000 m3/h

Conformes ErP - UVNR - Moteur EC variable ErP 2018 compliant
UVNR - Variable EC Motor
Moteur ECM Débit ou pression régulés GTC Modbus OPTAIR® CTA VIM

  • Low consumption ECM motor
  • 25 mm double skin insulation
  • Optional M5, F7 or F9 filtration
  • Reaction freewheel fan
  • Modular design

Application

Introduction of fresh air, filtration, heating and cooling.
Indoor or outdoor installation.
Treated air temperature -25 to +40°C.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates of 500 m3/h at 12,000 m3/h.
6 sizes: 18 / 40 / 55 / 75 / 95 / 120.

Regulations and management
  • Regulation by integrated CORRIGO automaton specific to VIM .
  • 3 operating modes: variable flow (VAV), constant flow (CAV), constant pressure (COP).
  • Communicating Modbus RTU on RS485 or Modbus TCP/IP, BACnet IP or MSTP port.
  • ETD remote touch control.
Settings
  • Interior without roof: D right easement - G left easement.
  • Exteriors with mounted roof: EXD right easement - EXG left easement.
Additional modules
  • KB air treatment modules:
    • KBEI electric battery module
    • KBEC hot water coil module
    • KBER reversible water battery module
  • KPCA 3-stage filtration module: Metallic / M5 + F7 / F9 + Activated carbon cartridges.
  • KSIL silent module.

Construction
  • Modular structure in aluminum profile.
  • In-line construction, rectangular or circular connection.
  • Double skin panels equipped with peripheral seal:
  • Exterior in pre-painted zinc-plated steel, dark gray color RAL7024, corrosion resistance RC5, ultraviolet resistance RUV3 according to EN 10169.
  • Z275 galvanized steel interior.
  • Insulation with thick glass wool. 25 mm, density 24 kg/m3.
  • Thermal conductivity 0.035 W/(mk) (20°C).
  • A1 fire classification according to standard EN 13 501.1.
  • Freewheel reaction fan made of non-combustible material. Mono 230V or Tri 400V ECM motor depending on size.
  • Switch mounted/hardwired.
  • Module delivered on feet (40 to 75) or frame (95 to 120).

2-stage filtration
  • Metal pre-filter: FIME thickness 48 mm.
  • Pleated pre-filter: FIFI M5 ePM10 50% thickness 48 mm.
  • FIFI F7 ePM1 55 minifold filters% or FIFI F9 ePM1 80% thickness 98 mm.

Registers (accessory)
  • Manual or motorized control.
  • Antifreeze protection for water batteries, mounted on the suction side.
  • Closure of the network in application of article CH38, mounted on blowing.

NEW: KFIL filtration module
  • Two filtration stages to choose from Metallic / M5 / F7 / F9

NEW: KATH Athermal catalysis decontamination module
  • Incorporates decontamination technology developed by Calistair, a specialist in air purification.
  • System composed of reactors with impregnated cellular structures and UV-C lamps
  • Allows the elimination of chemical pollutants, viruses and other micro-organisms by chain reaction and without generation of toxic products or by-products
  • Designed for applications aimed at strengthening the protection of human and animal health, as well as the protection of industrial products and processes: EHPAD, hospitals, medical homes / Poultry breeding, farms / Electronic or pharmaceutical industry, etc.

KB Battery Modules

KBEI - Electric battery module
  • 304L stainless steel resistances.
  • Safety thermostats: one thermostat with automatic reset 85°C, one thermostat with manual reset 120°C.
  • Control by pulse train.
  • Post-ventilation.
  • Separate Tri 400V power supply with safety switch.

KBEC - Hot water coil module
  • 2 or 4 row battery, with copper tubes, aluminum fins on a galvanized steel frame; threaded connection tubes.
  • Right or left connection in the direction of air flow.
  • Anti-freeze protection by contact probe.
  • Battery(ies) mounted on slide accessible via side hatch.

KBER - Cold or reversible water battery module
  • ER cold or hot water batteries.
  • 4 row battery, with copper tubes, aluminum fins on a galvanized steel frame; threaded connection tubes.
  • Right or left connection in the direction of air flow.
  • Change-over thermostat.
  • Anti-freeze protection by contact probe.
  • Battery(ies) mounted on slide accessible via side hatch.
  • Stainless steel condensate tray and droplet separator.

Silent module
KSIL - Acoustic baffle module
  • 200 mm thick baffles.
  • Rock wool 50kg/m3 protected by an anti-defiber glass veil.
  • A1 fire classification.
  • Kitchen option:
    • M0 (A1) expanded metal protection to facilitate cleaning and maintain acoustic performance.

Air treatment selection
KSEF ECOWATT® 18 / 40 / 55 / 75
Indoor model without roof




Outdoor model with roof




Size A B C D E F G J M N O P Weight (kg)
Without roof With roof
KSEF ECOWATT® 18 985 644 584 538 700 100 33 154 607 985 784 796 63 73
KSEF ECOWATT® 40 1135 695 635 635 795 100 33 154 757 1135 835 891 88 120
KSEF ECOWATT® 55 1210 981 921 635 795 100 33 154 832 1210 1121 891 130 161
KSEF ECOWATT® 75 1270 981 921 921 1081 100 33 154 892 1270 1121 1177 141 156



KSEF ECOWATT® 95 / 120 / 200
Indoor model without roof




Outdoor model with roof




Size A B C D E F G N O P Weight (kg)
Without roof With roof
KSEF ECOWATT® 95 1478 1306 1226 967 1202 155 33 1478 1446 1308 230 255
KSEF ECOWATT® 120 1959 1306 1226 1272 1507 155 33 1959 1446 1613 353 385

Close Open Detailed specifications

Close Open Public tariff price

Close Open Installation instructions

Close Open Performance / Environment Certificates

Declaration of performance (DOP)

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

Close Open Prescription assistance

X