REVA

Rectangular registers

Galva - VAV or CAV - With regulator

REVA View larger

REVA

Rectangular registers


Galva - VAV or CAV - With regulator

PIC-debit-constant-debit-variable.jpg

  • Precise airflow regulation
  • Incorporates a differential pressure regulator
  • Adjustable flow rate range on site
  • Real-time flow display
  • Low pressure drop

Applications:

Ventilation and air conditioning installation.
Use in blowing or recovery.
CAV: maintaining a precise constant flow rate.
VAV: variation of the flow rate according to an air quality or temperature setpoint.
Operation independent of upstream pressure.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Dimensions LxH: 200x200 to 1600x1000.
Flow rates: 200 to 57,000 m3/h.
Operating range air speed 2 - 10 m/s
REVA: bare register.
REVA I: isolated register.

Body + fins
  • ATC6 Body Sealing - Class 4 Shutter
  • Made of galvanized steel.
  • 38 mm connecting flanges with oblong holes in the 4 corners.
  • Measuring pins.
  • Insulated version: double skin galvanized steel thickness 30mm, elastomer insulation (B-s3,d0).
Servomotor + GRUNER pressure regulator
  • 24 VDC/VAC power supply, IP42.
  • 0–10V or 2–10V control signal.
  • Digital display / Adjustment button / Function selection button.
  • Real-time display of flow rate.
  • Operating conditions: temperature 0°C to +50°C / 5 to 95 % HR.
  • Modbus RTU, BACnet MSTP communicating servomotor version, please contact us.
Servomotor + BELIMO pressure regulator
  • Power supply 24 VDC/VAC, 50/60 Hz, IP54.
  • 0–10V or 2–10V control signal.
  • Servomotor configuration made easy by the Belimo Assistant app.
  • Operating conditions: temperature 0°C to +50°C / 5 to 95 % HR.
  • Modbus communicating servomotor version, contact us.
CR24-B1 / CR24-B2
  • BELIMO room thermostats.

Operating principle:
VAV – Ventilation / Air Quality
  • The system allows the fresh air flow to be precisely adapted based on a CO2 measurement (proportional) or a presence detector (total or partial).
  • Depending on the output signal, the flow rate adjusts between precisely set minimum and maximum values.
  • A differential pressure regulator is used to detect changes in duct pressure and adjust the position of the flap so that the set flow rate is maintained.
  • Pressure fluctuations therefore have no impact on the air quality in the room.

VAV – Heating / Air Conditioning
  • The heat supply is provided in whole or in part by the air vector.
  • The system allows the air flow to be precisely adapted between a minimum and a maximum depending on the load thanks to cascade regulation.
  • A room thermostat (regulator) sends a signal C representing the difference between setpoint B and temperature measurement A to the servomotor regulator to deliver the necessary flow rate.
  • A differential pressure regulator is used to detect changes in duct pressure D and to adjust the position of the flap so that the set flow rate E is maintained.
  • Pressure fluctuations therefore have no impact on the room temperature.
REVA


Weight (in kg)
HxB (mm) 200 250 300 400 500 600 700 800 1000 1200 1400 1600
200 4.6 5 5.5 6.5 7.5 8.4 9.3 10.3 11.2 - - -
250 - 5.5 6.2 7.1 8 9 10 10.9 11.9 - - -
300 - - 6.8 7.7 8.7 9.6 10.6 11.6 12.5 - - -
400 - - - 9 10 10.9 11.9 12.9 14.6 16.2 17.8 19.4
500 - - - - 11.3 12.2 13.2 14.2 15.6 17 18.4 20
600 - - - - - 13.5 14.5 15.5 17.4 19 20.6 22.2
700- - - - - - - 15.8 16.8 19.2 21 22.8 24.6
800 - - - - - - - 18.1 21 23 25 27
1000 - - - - - - - - 24.2 26.6 29 31.4

Close Open Detailed specifications

Text catalog pages (CT)

Close Open Public tariff price

Price catalog pages (CP)

Close Open Installation instructions

Installation instructions (NT) Other

Installation instructions (NT) - Old version

Close Open Fire / Smoke extraction certificates

Fire classification report (PVFEU)

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

X