VFTM PR

Old ranges

For regulated pressure IP55

FLAG Obsolete
VFTM PR View larger

VFTM PR

Old ranges


For regulated pressure IP55

CSTB.jpg COP.jpg GTC-MODBUS.jpg
  • Integrated pressure sensor and switch-disconnector
  • Single-phase 230V or three-phase 400V power supply
  • Compatible with all TN, TT and IT neutral systems
  • Integrated and disconnectable RFI filter
  • Gas solenoid valve control
  • IP55

Applications:

Maintains constant aeraulic pressure by acting on the speed of a 230 / 400V single-speed three-phase asynchronous motor.


  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

VFTM PR mono: single-phase 230V 50 / 60Hz drive power supply + earth, 230V three-phase motor output.
  • 7 models from 0.18 to 2.2kW.
  • Integrated pressure sensor: operating range 90 to 300Pa.

VFTM PR tri: three-phase drive power supply 400V 50 / 60Hz + earth, three-phase motor output 400V.
  • 10 models from 0.37 to 7.5kW.
  • Integrated pressure sensor: operating range 80 to 800Pa.

Description
  • Frequency converter for three-phase squirrel-cage asynchronous motor.
  • Incorporates a pressure sensor, self-supplied by the drive (range 90-300Pa for VFTM PR mono and 80-800Pa for VFTM PR tri).
  • Adjustment of the pressure setpoint by potentiometer on the front panel.
  • The motor output is continuously adjusted (PI regulation) according to the pressure measured in the aeraulic network; The set pressure setpoint is thus automatically respected regardless of changes in the network (fouling, etc.).
  • 3-point padlockable switch-disconnector on the front (except on VFTM PR tri 5.5 and 7.5).
  • Front display: access to parameters and indication of states and faults.
  • Additional outputs available:
    • 1 analog output: 0-10Vdc or 4-20mA for controlling a slave drive.
    • 2 programmable dry contact outputs (fault, on, gas solenoid valve).
  • Incorporates configurable protection against overloads and short circuits.
  • Integrated RFI / EMC network filter for connection to TT or TN neutral system; on IT neutral mode, deactivate this filter.
  • Integrated Modbus communication.
  • Factory setting.
  • Electrical insulation: class 1.
  • Protection class IP55.
  • Operating environment: -10 to + 40 ° C (at 8kHz); other values consult us.
  • To be combined with fans fitted with a 230V / 400V three-phase 1-speed motor.
  • Allows to maintain a constant pressure by acting on the speed of the engine.


Cut

a

b

c

G

H

T1

210

240

183

192

218

T2

215

297

212

197

277

T3

230

340

242

212

318

T4

320

512

276.5

279

480

Dimensions G and H = fixings

Close Open Detailed specifications

Text catalog pages (CT)

Close Open Installation instructions

Installation instructions (NT)

Installation instructions (NT) Other

X