CAD HR CLASSROOM

Old ranges

Counter flow - Decentralized - ECM

FLAG Obsolete
CAD HR CLASSROOM View larger

CAD HR CLASSROOM

Old ranges


Counter flow - Decentralized - ECM

PIC-ERP-2018.jpg PIC-Regulation-Plug-Play recuperation-nrj F400-F200
  • Simplified installation
  • Bypass 100% for freecooling
  • Antifreeze protection by modulating bypass
  • Low consumption ECM motor
  • Integrated electric post-heating battery
  • Low noise level - Built-in silencer
  • Thermal efficiency up to 95%


Application

Decentralized air supply and extraction with energy recovery in tertiary premises.
Installation in the room against the exterior wall.
Ideal for renovating schools, nurseries, offices, small businesses, etc.

  • Description

  • Dimensions

  • Documentation

A size up to 1000 m3 / h.
Horizontal construction allowing two types of connection:
RH: horizontal connection Ø315 on the rear.
RV: vertical connection Ø315 on the top.
TAC5 regulation, communication possible via Modbus RTU- RS485,
Modbus TCP / IP, KNX type TP, application for smartphone, tablet or PC (Android, IOS, Windows 7/8/10).


Construction
  • Box with self-supporting structure in galvanized steel.
  • The three access panels below are 30 mm double skin, thermal insulation made of fire-retardant rock wool (Euroclass A1).
  • Inside the unit has been designed to optimize the sound insulation in melamine foam, density 9.5kg / m3, M1 classification.
  • Exterior finish prepainted steel polyester type (5μm primary +
  • 20 μm polyester) color RAL 9022.
    • Perforated diffusion sheet on the front, and recovery on the right side.
    • Bottom panel allowing access to filters, exchanger and control cabinet.
  • Single inlet action fan.
  • Interior finish in galvanized steel.
  • Access to filters and exchanger from below.
  • Condensate collection tray equipped with a condensate drain pump (factory connected) and Ø8 mm drain pipe.
  • Bypass 100% equipped with a proportional motor.

Motorization
  • Low consumption, direct current, single phase 230V ECM motor. Electronic thermal protection - manual reset.

Exchanger
  • High efficiency air / air countercurrent heat exchanger made of "sea water resistance" aluminum for an operating temperature of up to 80 ° C. Thermal efficiency up to 95%.
  • Antifreeze protection of the exchanger integrated into the regulation by progressive opening of the bypass, making it possible to maintain a minimum temperature of 1 ° C at the discharge.

Filters
  • M5 filters on extraction and M5 on supply. Easily accessible from below.

Integrated post-heating electric coil
  • Power 3Kw Mono 230V.
  • Delivered fully pre-wired, and connected to the regulation.
  • Proportional regulated power
    • Thermal protection with automatic reset (80 ° C) and manual reset (115 ° C).
  • Motorized damper on the fresh air inlet, mounted, wired, controlled by the regulation, avoids air inlet when the unit is stopped.

TAC control ready to plug in
  • Complete regulation allowing 2 main operating modes:
    • LS MODE - VARIABLE FLOW RATE
    • AC MODE - CONSTANT FLOW
  • The operation of the exhaust fan is slaved to the supply fan. Its flow rate corresponds to a percentage of the flow rate of the supply fan (100% for identical flow rates).
  • Programmable regulation from the remote control.
CAD HR CLASSROOM RH

Weight 206 kg

CADHR-CLASSROOM-dim
Dble-flux-légende


CAD HR CLASSROOM RV

Weight 246 kg

CADHR-CLASSROOM-sortiesV-dim
Dble-flux-légende