PILOT CTA DAD

Management system

CTA fire management

DAD S4 T1 - Autonomous detector View larger

PILOT CTA DAD

Management system


CTA fire management

  • Complete system
  • Meets article CH38 in ERP
  • Components compliant with NF standards
  • For CTA VIM and other brands


Application

Fire safety regulations in public buildings - Article CH38 Filters
- For AHU over 10,000 m3/ h
- For AHU serving rooms reserved for sleeping
- For a set of AHU treating in total for the same room more than 10,000 m3/ h

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

A smoke detector (OX-8) mounted in a duct box (BDG1) signals the presence of smoke to the DAD (DAD S4 T1).
In this case, the DAD provides:

  • Stopping the fan
  • The closing of a 24V all-or-nothing motorized metal damper with return spring, located at the outlet downstream of the filters
  • Cutting off the power supply to the heating batteries (if any)

Installation example


DAD S4 T1:

180 x 200x 72mm - Total net weight: 2,800g

DAD-dim


BDG1

BDG-dim

Close Open Detailed specifications