GA - GA GAZ - GG

Flexible ducts

Galva or aluminum - Semi rigid

GA - GA GAZ - GG View larger

GA - GA GAZ - GG

Flexible ducts


Galva or aluminum - Semi rigid

  • GA: Flexible non-insulated aluminum semi-rigid conduit M0 - 3 m
  • GAS GAS: Flexible non-insulated aluminum duct for M0 gas - 1.5 m
  • GG: Galvanized steel flexible duct not insulated M0 - 3 m
  • GA ISO: Flexible insulated aluminum conduit M0 / M0 - 3 m
  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

GA: Flexible non-insulated aluminum semi-rigid conduit M0 - 3 m
  • Classified A1: incombustible.
  • Aluminum, thickness 12/100 mm.
  • Complies with DTU 68-3.
  • Packaged in lengths of 3 m compressed to 0.6 m.
  • Temperature resistance: -30 ° C to + 300 ° C.
  • Radius of curvature :
    • Ø 315: R ≈ 2 Ø.

GAS GAS: Flexible non-insulated aluminum duct for M0 gas - 1.5 m
  • Classified A1: incombustible.
  • Semi-rigid aluminum, QUALIGAZ A5 approved, 15/100 mm thick.
  • Complies with DTU 68-3 (VMC Collective housing special standard gas).
  • Packaged in lengths of 1.5 m compressed.
  • Operating temperature: 250 ° C.
  • Peak temperature: 300 ° C.
  • Radius of curvature: R ≈ 1Ø.
GAS GAS - 118/125:

boiler connection, internal diameter 118 mm, external diameter 125 mm.

GAS GAS - 125/132: boiler connection, internal diameter 125 mm, external diameter 132 mm.

  • Supplied with a male sleeve for connecting the boiler.

GG: Galvanized steel flexible duct not insulated M0 - 3 m
  • Classified A1: incombustible.
  • Galvanized steel, thickness 8/10 (Ø80 to 200), 10/10 (above).
  • Complies with DTU 68-3.
  • Packaged in lengths of 3 m, compressed up to Ø 200.
  • Temperature resistance: -30 ° C to + 300 ° C.
  • Radius of curvature :
    • Ø 315: R ≈ 2 Ø.

GA ISO: Flexible insulated aluminum conduit M0 / M0 - 3 m
  • Phonically isolated.
  • Classified A2-s1-d0 (M0 / M0).
  • Indoor / outdoor: aluminum, 12/100 mm thick, 25 mm thick glass wool insulation.
  • Packaged in lengths of 3 m, uncompressed.
  • Temperature resistance: -30 ° C to + 250 ° C.
  • Radius of curvature :
    • Ø 315: R ≈ 3 Ø.

GA ISO Acoustic data

Ø

mm

Attenuation by frequency band

125

250

500

1000

2000

4000

8000

80

3

6.5

128

25.7

32.9

45.9

57.3

100

2.5

5

11.5

30.5

40

21.5

11.5

125

2

4

10

29

38

20.5

11

160

1

3.5

9

27.5

29

12.5

8.5

200

0.5

2.5

7.5

26

34

18

10

250

0.5

2

6

24.5

32

17

9.5

315

0.5

1.5

18

23

30.5

15.5

9

400

0.5

1

17

21.5

29.5

14.5

8.5