Search a product :
New product
To be installed around plastic pipes (PVC, PE).
Intended to prevent the spread of fire when flammable pipes catch fire (temperature around 150 ° C) by ensuring the refractory sealing of these openings.
Restoration of the fire rating of a wall or slab traversed up to 180 minutes (MG2 A).
Use inside buildings.
Description
Dimensions
Documentation
Public Price
Software
References
MG2-A | ||||
---|---|---|---|---|
Pipe material | Diameter Ød (mm) | Wall concrete / aerated concrete ≥100mm | Concrete / aerated concrete slab ≥150 mm | Wall plasterboard type F ≥100mm |
PVC | 32-160 | EI 120 | EI 90 - EI180 | EI 120 |
PE | 32-160 | EI 120 | EI 120 - EI 180 | EI 120 |
MG2-A XL | |||
---|---|---|---|
Pipe material | Diameter Ød (mm) | Wall concrete / aerated concrete ≥100mm | Concrete / aerated concrete slab ≥150 mm |
PVC | 200-400 | EI 120 | EI 120 |
PE | 200-250 | EI 90 - EI 120 | EI 120 |
ØDn (mm) | 32 | 40 | 50 | 56 | 63 | 75 | 80 | 90 | 100 | 110 | 125 | 140 | 160 |
ØD1 (mm) | 48 | 58 | 68 | 74 | 80 | 93 | 110 | 125 | 132 | 140 | 173 | 187 | 206 |
L0 (mm) | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 |
Weight (kg) | 0.1 | 0.1 | 0.1 | 0.2 | 0.2 | 0.2 | 0.2 | 0.3 | 0.3 | 0.3 | 0.4 | 0.5 | 0.6 |
ØDn (mm) | 200 | 250 | 315 | 355 | 400 |
ØD1 (mm) | 271 | 321 | 396 | 436 | 481 |
L (mm) | 100 | 100 | 150 | 150 | 150 |
Weight (kg) | 2.7 | 3.2 | 7.0 | 7.8 | 9.6 |
Model | Mounting type | Material | Dimensions (mm) |
MG2 A | Solid slab / wall | Concrete / aerated concrete | Øn + 3 |
Flexible wall | Plasterboard type F | Øn | |
MG2 A XL | Solid slab / wall | Concrete / aerated concrete | Øn + 3 |
Detailed specifications
Text catalog pages (CT)
Public tariff price
Price catalog pages (CP)
Installation instructions
Installation instructions (NT)
Fire / Smoke extraction certificates
Fire classification report (PVFEU)
Performance / Environment Certificates
Commercial documents
Commercial leaflet (FCOM)
Detailed specifications
Text catalog pages (CT)
Public tariff price
Price catalog pages (CP)
Installation instructions
Installation instructions (NT)
Fire / Smoke extraction certificates
Fire classification report (PVFEU)
Performance / Environment Certificates
Commercial documents
Commercial leaflet (FCOM)