TEDH F400 ECOWATT® - TEDV F400 ECOWATT®

Roof fans F400 120

Centrifuges - Reaction - ECM < 24000 m3/h

TEDH F400 ECOWATT 450 View larger

TEDH F400 ECOWATT® - TEDV F400 ECOWATT®

Roof fans F400 120


Centrifuges - Reaction - ECM < 24000 m3/h

PIC-Conforme-ErP.jpg ErP 2018 compliant - UVNR
Variable EC motor
F400.jpg Conformite-europeenne.jpg debit-pression-regule.jpg GTC-modbus.jpg
moteur-ecm.jpg vmc-hygro.jpg logiciel.jpg

  • Low consumption ECM motor
  • High performance jet turbine
  • F400 120 approved without relay box and 400 ° C 1 / 2h C4
  • Integrated regulation VAV, CAV, COP, ASR
  • Flow or pressure display
  • Communicating ModBus
  • Continuous operation up to 120 ° C

CMV collective and tertiary housing.
Extraction of stale air from tertiary and industrial premises.
Ventilation and smoke extraction in professional kitchens.
Maximum temperature of the extracted air in permanent mode: 120 ° C.
In the current state of the standard, this range cannot be associated with an NF certified relay box.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates from 200 to 24,000 m3/h.
6 sizes: 355 / 400 / 450 / 500 / 630 / 710.

Models
  • TEDH F400 ECOWATT: horizontal discharge
  • TEDV F400 ECOWATT: vertical discharge
    • Engine and turbine not visible.
    • Less fouling of the immediate surroundings.

Versions
  • TEDH/V F400 ECOWATT manual control with potentiometer.
  • TEDH/V F400 ECOWATT VAV with flow display.
  • TEDH/V F400 ECOWATT COP with pressure display.
  • TEDH/V F400 ECOWATT CAV with flow display.
  • TEDH/V F400 ECOWATT ASR with pressure display and specific terminal block for integration into kitchen flow control systems, ASR1 and ASR2 ECOWATT.


OPTIONS - ANTI-CORROSION TREATMENT


TEDH - TEDV F400 ECOWATT - Main spare parts


Construction
  • High performance reaction turbine in galvanized steel.
  • Convergent/divergent type suction horn for aeraulic optimization and increased turret efficiency, with reduced noise levels.
  • Direct coupling on the motor shaft.
  • Motor controller fixed on a sealed rejection face.
  • Plate, arm and motor support in galvanized steel.
  • 4 lifting legs depending on model.
  • 4 lifting slings.
  • Arm covers in pre-painted sheet metal, gray RAL 7024:
    • Neat finish of the turret.
    • Easy disassembly to access turret mounting points.
  • Protective mesh in pre-painted galvanized steel sheet RAL 7024 gray. Meshes conforming to standard NF EN ISO 12499.
  • ABS PMMA cap, grey RAL 7024:
    • Valuable aesthetics.
    • Motor and display protection.
    • Excellent resistance to UV rays and bad weather.
    • Very good impact resistance.
  • Vertical discharge version: addition of 3 deflectors in RAL 7024 pre-painted sheet metal delivered factory-assembled (TEDV F400 ECOWATT model) or available as a kit for on-site assembly (KRVT).
  • The RAL 7024 grey pre-painted sheet metal is in the atmospheric corrosivity category C5 according to NF EN ISO 12944-2.

Motorization
  • ECM motor, class F, with remote IP55 controller:
    • Single-phase 230V 50/60Hz power supply controller for sizes 355 to 450.
    • Three-phase 400V 50/60Hz power supply controller for sizes 500 to 710.
  • Thermal protection integrated into the controller.

Communication
  • ModBus RTU in RS485 port.

ETDZ Remote control
  • IP21 touch ModBus control, 3m RJ12 cable supplied.
  • M/A function.
  • 0-10V speed control in VAV mode.
  • Display of the setpoint and rotation speed.
  • Display of consumption and faults.
  • Shockproof case with magnetic attachment provided.

Flow or pressure display
  • VAV display of the measured flow rate in m3/h. Accuracy ±2.5%.
  • CAV display of the measured flow rate in m3/h. Accuracy ±2.5%.
  • COP display of the measured pressure in Pa. Accuracy ±2.5%.

Smoke extraction operation
  • The TED F400 ECOWATT is approved for the extraction of hot gases and fumes in the event of a fire. This operating mode is automatic and does not require any settings: in the event of gas extraction at a temperature > 200°C, the turret will automatically switch to GV with its internal thermal protections inhibited.
  • The smoke extraction mode can also be triggered manually with a BDRA type control box.
  • CAV/VAV/COP modes are no longer supported.

Factory-fitted and approved F400 120 electrical equipment:
  • C1-CR1 cable protected by flexible external sheath (excellent UV resistance).
  • INTZ : padlockable proximity switch, with 2 auxiliary contacts (1 NO and 1 NC), visibility of the rotary button only and increased protection against bad weather.
  • PTHV-A : pressure transmitter with visible flow or pressure display. Integrated under the cap, it displays the flow rate in VAV control.
  • VCHV-A : pressure or flow regulator for COP or CAV regulation with display, integrated under the cap.

F400 120 approved mounting accessories
  • TCDZ 01 to 09, SILS silencer, POPM blanking plate, KRVT vertical kit.
  • TCDZ 12 : pressure relief shutter in pre-painted steel RAL 7024 C5. Ensures good air and water tightness when the turret is stopped. Option supplied mounted on the TEDV ranges - Provide as many TCDZ 12 as there are discharge faces.
  • TCDZ 14 : pressure relief shutter in pre-painted steel RAL 7024 C5. Ensures good air and water tightness when the turret is stopped. Accessories to be mounted on the TEDV ranges already delivered - Provide as many TCDZ 14 as there are discharge faces.
  • TCDZ 15 : pressure relief flap + vertical deflector in pre-painted steel RAL 7024 C5. Ensures good air and water tightness when the turret is stopped. Accessories to be mounted on the TEDH ranges already delivered - Provide as many TCDZ 15 as there are discharge faces.
  • POPM : RAL 7024 C5 pre-painted steel blanking plate with one rejection face for TEDH for installation of the turret near a wall (or an obstacle to gas evacuation), or in a corner or between 2 other turrets with 2 POPM. Allows significant space saving and avoids the rejection of air and dirt directly onto the wall.
  • Laboratory tests have verified that the vertical discharge kit and the one-sided blanking plate have no impact on the aeraulic, acoustic and electrical performance of the turret.

Smoke extraction fan selection
TEDH F400 ECOWATT

Model

A

B

CH

D

E

F

P

Weight (Kg)

355

540

570

754

289.1

450

30

146

34

400

540

609

754

325.8

450

30

169

44

450

660

684

864

366.5

570

30

190

57

500

660

700

867

407.3

570

30

198

83

630

800

805

1045

513.1

668

30

234

106

710

946

1089

1223

577.9

830

40

273

165




TEDV F400 ECOWATT
TEDV-ECO-dim.png

Model

A

B

CV

D

E

F

Weight (Kg)

355

540

570

901

289.1

450

30

38

400

540

609

926

325.8

450

30

49

450

660

684

1051

366.5

570

30

63

500

660

700

1070

407.3

570

30

94

630

800

805

1279

513.1

668

30

116

710

946

1089

1489

577.9

830

40

179

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

Close Open Prescription assistance

EASYVENT
Access the software online Media locked
ALL APPLICATIONS
LOGO_EASYVENT-WEB-bord-blanc.jpg Selection of fans and AHU
  • Creation of complete technical sheets with thermal data (CTA), fan operating points, acoustic characteristics and dimensional drawings.
Other products: permanent updates
BSP F400
CAB ECOWATT
CAD HR SLIM
CAD O INTEGRAL
CBM
CBM RE
CGT
CAT N F400
CHGT F400 - CHGT F300
CHRB/TN - CRVB/TN
CMB - CMT
CRHB-CRVB ECOWATT
CTB
CVAB N - CVAT N
CVAB N - CVAT N ECOWATT
FR F400
HCTB - HCTT - HCTT ATEX
HDB ATEX
HGHT F400 / F200
HGTT-V
HXBR - HXTR
HXBR ECOWATT
KABB - KABT
PURECLASS
TCBB - TCBT
TCTB ATEX - TGT ATEX
TCDH ATEX
TD - TD ECOWATT
TD ATEX
TD SILENT - TD SILENT ECOWATT
TGHT F400 - THGT F200
TGT
TGT ATEX
THC - THC ECOWATT
THGT HATCH F400
TRB - TREB
TXBR ECOWATT
ECOWATT WIND
VENT-NK - VENT-VN


OPTAIR Ventilation
Download OPTAIR Ventilation Media locked
VMC SMOKE EXHAUST
OPTAIR-Ventilation.png Selection of turrets and boxes: KDT / KSH / TCD / KUBAIR / TED
  • VScreation of a technical sheet per fan including the requested operating point on the curve, the technical and acoustic characteristics, and the overall dimensions
  • Printing possibility
  • Link to all technical pages Catalog
KCTR F400
KDTA BP
KDTA F400
KDTR BP
KDTR F400
KSHA
KSHP
KSHR
KUBAIR F400 CC
KUBAIR F400 ECOWATT CC
KUBAIR F400 ECOWATT MV
KUBAIR F400 MV
TCDH F400
TCDV F400
TEDH F400
TEDH F400 ECOWATT
TEDV F400
TEDV F400 ECOWATT
3 BRASSEURS

Close Open 3 BRASSEURS

Restaurant chains

59 - North

Close Open ECOLE DE TOUSSIEU - CONSTRUCTION RESTAURANT SCOLAIRE ET 4 CLASSES

Community restaurants / RIE

69 - Rhône

ECOLE HOTELIERE DE BIARRITZ

Close Open ECOLE HOTELIERE DE BIARRITZ

Specialized education

64 - Pyrénées-Atlantiques

LYCEE B. FRANKLIN - ORLEANS

Close Open LYCEE B. FRANKLIN - ORLEANS

High schools

45 - Loiret

Close Open LYCEE FRANCOIS CEVERT - ECULLY - RESTRUCTURATION

High schools

69 - Rhône

MEDIATHEQUE L'AGORA - METZ

Close Open MEDIATHEQUE L'AGORA - METZ

Media library

57 - Moselle

THE ROSTER - ANNECY

Close Open THE ROSTER - ANNECY

Independent commercial catering

74 - Haute-Savoie

X