ARPB

Battery regulation

Power and regulation cabinets - Electric coils

FLAG Obsolete
ARPB View larger

ARPB

Battery regulation


Power and regulation cabinets - Electric coils

Plug-and-play regulation Temperature regulation

  • Ready-to-use cabinet
  • Limits energy consumption
  • No magnetic disturbance

Application

Allows the power supply, power regulation and protection of the electric heaters and the fan.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Power cabinet for three-phase batteries from 9kW (13A) to
150kW (217A):

Caliber

Number of floors

Power (kW) / Intensity (A)

1

2

3

4

5

15kW (22A)

15/22

24kW (35A)

24/35

36kW (52A)

36/52

24 + 12/35 + 17

3x12 / 3x17

45kW (65A)

27 + 18/39 + 26
30 + 15/43 + 22

48kW (69A)

2x24 / 2x35

54kW (78A)

2x27 / 2x39

60kW (87A)

2x30 / 2x43

2x24 + 12 / 2x35 + 17

63kW (91A)

2x27 + 9 / 2x39 + 13

72kW (104A)

3x24 / 3x35
2x27 + 18 / 2x39 + 26

75kW (108A)

2x30 + 15 / 2x43 + 22

84kW (121A)

3x24 + 12 / 3x35 + 17

90kW (130A)

3x30 / 3x43

96kW (139A)

4x24 / 4x35

105kW (152A)

3x30 + 15 / 3x43 + 22

120kW (173A)

4x30 / 4x43

150kW (22A)

5x30 / 5x43

Other characteristics (power and number of stages): contact us.


Description
  • Progressive control, chrono-proportional regulation by triac.
  • Three-phase power supply 400V 50 / 60Hz.
  • IP54 cabinet, hinged door, mounted cable glands, wall mounting kit.
  • Three operating modes:
    • Integrated 0… 30 ° C set point (probe connection).
    • Remote 0… 30 ° C set point (probe + potentiometer connection).
    • Control by external 0… 10V signal (ARSC connection).
  • Padlockable switch-disconnector on the front.
  • Controls (battery on / off and ventilation on / off) on the front or remote with control by indicator lights.
  • Integrated thermal protection.
  • The cabinet slaves the operation of the battery to that of the ventilator (post ventilation).
  • Control terminals for regulation probe and min and max temperature limitation probe.
  • Safety terminals: pressure switch, battery safety thermostats, min / max duct probe.
  • Power terminal blocks: 36kW (52A) for 1-stage cabinets, or 30kW (43A) maximum per stage.
  • Multistage sequencer (from 2 to 5) with its power contactors (for power cabinets> 36KW).
ARPB-dim

Power

A

B

C

D

E

15kW

530

430

255

455

325

24 and 36kW

645

436

305

555

330

45 to 84kW

847

636

355

755

530

90 to 150 kW

1056

852

405

964

746

Close Open Installation instructions

Installation instructions (NT)