TGT HATCH

Axial fans

Tubular - AC < 130,000 m3/h

Flag Nouveau
TGT HATCH View larger

TGT HATCH

Axial fans


Tubular - AC < 130,000 m3/h

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates from 3,400 to 130,000 m3/h.
9 sizes: Ø 500 / 560 / 630 / 710 / 800 / 900 / 1000 / 1120 / 1250 mm.
Air direction A (motor/fan).
ErP data available in Easyvent.

Construction
  • Box incorporating a long shell made of hot-dip galvanized steel sheet in accordance with EN 1461. Double-skin panels with 50mm polyurethane insulation.
  • Box and ferrule for corrosion class C4 environments.
  • High-efficiency injected aluminum propeller 3, 5, 6, 7, 9 or 12 blades dynamically balanced according to ISO 14694: G6.3. with variable inclination angles when stationary except for 2-pole motor, to respond precisely to all flow/pressure requirements. Certified TGT fan AMCA.
  • The standard design incorporates a base.
  • Waterproofing 3/h/m² at 50Pa.
  • Insulation U = 0.42W/(m2K) without thermal bridge.
  • Snow load SL 1000 at -25°C according to EN 12101-2.
  • Wind resistance WL 1,500 (sizes 500 to 1,000) or 1,000 (sizes 1,120 and 1,250) according to EN 12101-2.
  • 2-speed opening mechanism 20,000 cycles with opening/closing limit switches for external control box type control CCAC (accessory).
  • Connection boxes IP65 independent for motor with disconnector and for servomotors (220-240V 50Hz IP65).
  • The cover must be controlled to open before the fan starts and to close after it stops. The control box CCAC (accessory) performs this sequence.

Motorization
  • Three-phase asynchronous motor directly coupled to the propeller, without thermal protection. 1-speed motors by default
  • Possible control by frequency variation.
  • 1-speed motor with B3 feet, IP55, class H:
    • three-phase 2, 4 or 6 poles 230/400V, 50/60Hz* up to 3 kW.
    • three-phase 2, 4 or 6 poles 400V, 50Hz above 3 kW.
  • 2-speed motor (Dahlander windings) with B3 legs, IP55, class F:
  • three-phase 2/4, 4/6, 4/8 or 6/12 poles 400V, 50Hz.

* According to characteristics

  • The engine should start after 20 to 36 seconds after the lid opening request, depending on the product characteristics. The control box CCAC manages this sequence.

Option
  • Painting according to RAL code.
  • Engines with preheating resistors, PTC or PTO sensors.
TGT HATCH



Size Dimensions (mm)
A H B C ØD1 ØD2 E N F M G J
500 1076 1058 1032 1143 500 560 1009 12 12 4 14 50
560 560 620
630 630 690
710 1256 1058 1212 1325 710 770 1190 16 12
800 800 860
900 1455 1164 1412 1550 900 970 1390 16 15
1000 1000 1070
1120 1704 1394 1662 1815 1120 1190 1640 20 15
1250 1250 1320
X