TJHT F400 - TJHT F200

Axial fans F400 or F200

Circular transfer jet fans - AC < 36,000 m3/h

TJHT F400 - TJHT F200 View larger

TJHT F400 - TJHT F200

Axial fans F400 or F200


Circular transfer jet fans - AC < 36,000 m3/h

ErP not applicable - Smoke extraction exclusively ErP not applicable
Smoke extraction exclusively
European compliance F400-F200.jpg

  • Approved F400 120 or F200 120
  • Integrated sound attenuators

Application

Movement of large volumes of air in covered parking lots, in comfort and smoke extraction.
Ambient air temperature between -20 ° C and + 40 ° C.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates from 4,500 to 36,000 m3/h.
Three models: F400 120, F200 120 or standard non-certified.
7 sizes Ø 315 / 355 / 400 / 450 / 500 / 560 / 630.
1 or 2 speed motors.

Construction
  • Sizes 315 to 400
    • Fan ferrules and support feet in Magnélis ZM 310.
    • Suitable for corrosion class C5 environments.
  • Sizes 450 to 630
    • Fan shells and support feet in steel according to EN 10130-99 and protection by hot-dip galvanization according to EN 1461:1999.
    • Suitable for corrosion class C4 environments.
  • 6-blade reversible propeller in die-cast aluminium according to EN 1706 and balanced according to ISO 14694: G 6.3.
  • Construction incorporating two circular acoustic attenuators made of galvanized steel sheet.
  • Fixing feet supplied as standard.
  • Upstream and downstream protective grilles supplied as standard.
  • For transport, fans up to size 400 are delivered assembled. From size 450 to 630, they can be delivered in 3 pieces to be assembled on site.

Motorization
  • Asynchronous motor directly coupled to the propeller:
    • Three-phase power supply 400V-50Hz.
    • F400 120 IP 55 class H or F200 120 IP 55 class F engine.
    • 1 speed 2 poles or 2 speeds 2/4 poles (Dahlander winding).
  • Corrosion class C3.
  • Approved F400 120 or F200 120 outdoor connection box mounted and wired.

Smoke extraction fan selection

TJHT-dim
TJHT-dim1

Model

A

B

C1 *

C2 **

D

E

H

L

L1

L2

Weight***
(Kg)

315

310

405

236

279

385

485

397

1754

1810

1967

57/57

355

310

445

259

302

425

525

437

1754

1810

1967

76/76

400

310

506

283

326

486

586

498

1754

1810

1967

89/89

450

539

556

313.5

362.5

536

636

548

2499

2055

2712

133/134

500

549

620

343.5

392.5

600

700

612

2499

2055

2712

165/166

560

669

680

376

425

660

760

672

3019

3072

3232

220/223

630

769

750

422

480

730

830

742

3119

3175

3332

290/311

* Junction box
** Proximity switch
*** Mono / two-speed

Close Open Detailed specifications

Close Open Installation instructions

Installation instructions (NT)

Close Open Fire / Smoke extraction certificates

CE smoke extraction certification (CCCE)

Close Open Performance / Environment Certificates

Close Open Commercial documents

Commercial leaflet (FCOM)

IKEA - CAEN

Close Open IKEA - CAEN

Shopping centers

14 - Calvados


Installed products:


PARKING ANTONIN PONCET (702 PLACES) - LYON

Close Open PARKING ANTONIN PONCET (702 PLACES) - LYON

Tertiary car parks

69 - Rhône

X